Introduction Products to zone - 2 Magnetic switch
Magnetic contact - maker of type GC-MS1
Technical description of the arrangement
The contact - maker is made in accordance with CSN EN 50 014 and CSN EN 50 021. The contact - maker is intended to switch circuits in the 2nd ZONE. Assuming nothing of mechanical straining. The contact - maker is produced in 2 variants without outer scroll and with outer scroll M10. The connector cable must to be properly fixed after exiting out of the contact - maker. The operational outdoor temperature -30°C up to +55°C. Electric circuit of the contact - maker can be protected by a safety fuse with rated current of max. 0,25 A. The contact - maker consists of a correed relay BV 551 which has got these electric parameters:
- Max. switched tension: ss. 175 V
- Max. switched current: ss 0,25 A
The circumfusion of reed contacts is implemented CHS EPOXY 531.
The case is made:
- of a duralumin round timber of average 8 mm in which a hole is drilled of diameter 6 mm
- of a duralumin round timber of average 10 mm in which a hole is drilled of diameter 6 mm and made an external scroll M10
Technical characteristics
Joining the outer circuits:
The magnetic contact - maker is manufactured with connector cables of lenght 5 up to 15 m. For a long dinstance connectin is possible to
prolong the connecting by the help of a connector box adapter authorized for ZONE 2. The max. load of switch contacts of the magnetic contact - maker at switching is 0,25 A. To connect the
magnetic contact - maker to outer circuits are used cables MK 2x 0,35 mm², SRO 2x 0,22 mm², SRO 3x 0,22 mm².
| Contact form | Price list | Manual | Video |
| Technical characteristics | |
|---|---|
| Max. switched tension | 175 V DC |
| Max. switched load | 3 W |
| Max. switched current | 0,25 A DC |
| Max. through current | 1,2 A DC |
| Rated voltage | 5 up to 24 V DC |
| Rated current | 4 up to 250 mA DC |
| Protection | IP 68 |
| Temperature limits (Ta) | -30 °C up to +55 °C |
| Temperature class | T 6 |
| Usage | ZONE 2 |
| Implementation | Ex II 3GD EEx nA II T6 T56°C FTZÚ 04 ATEX 0169X |
| The lenght of incoming cable | 5 up to 15 m |